1PosSSI/Analog
6.6 Functions of the 1PosSSI/Analog
ET 200S Positioning
290 Operating Instructions, 05/2007, A5E00124871-04
Control Signals: Display Current Values
Address Assignment
Bits 4.7 to 4.4 :
7 6 5 4 Bit
1 1 1 1
JOB 15 = Display current values
Byte 4
Bit 0: JOB_REQ
Byte 5 0: Residual distance
1: Actual speed
2: Causes of errors for POS_ERR and JOB_ERR
Feedback Signals: Display Current Values
Address Assignment
Byte 4 Bit 1: JOB_ERR
Bit 0: JOB_ACK
Bytes 5 to 7 In accordance with the selected feedback value:
With a residual distance of: - 8 388 608...8 388 607
With an actual speed of: 0...16 777 215
With causes of errors for POS_ERR and JOB_ERR
Byte 5: Causes of Errors for POS_ERR
Byte 6: Causes of Errors for JOB_ERR
Bits 7.3 to 7.0: MODE (= bits 0.7 to 0.4 from the control signals)
Bits 7.7 to 7.4: JOB (= bits 4.7 to 4.4 from the control signals)
Display current values: Causes of Errors for JOB_ERR
Error Number Meaning What to Do
35 Display current values: Selection unknown
37 Display current values: JOB 15 cannot be activated
with the latch function running.
See also
CPU/Master Stop and RESET State (Page 296)
Error Detection/Diagnostics (Page 291)