1PosSSI/Analog
6.10 Technical Specifications of the 1PosSSI/Analog
ET 200S Positioning
304 Operating Instructions, 05/2007, A5E00124871-04
Technical Data of the 1PosSSI/Analog
Data on the Digital Output
Output voltage
• Rated value
• 0 signal
• 1 signal
DC 24 V
≤ 3 V
≥ L+ -1 V
Output current
• 0 signal (leakage current)
• 1 signal
– Rated value
– Permitted range
≤ 0.3 mA
0.5 A
7 mA to 0.6 A
Switch rate
• Resistive load
• Inductive load
• Lamp load
100 Hz
2 Hz
≤ 10 Hz
Lamp load ≤5 W
Output delay (resistive load, output current 0.5 A)
• At 0 to 1
• At 1 to 0
typ. 150 µs
typ. 150 µs
Short-circuit protection of the output Yes
Threshold on 0.7 A to 1.8 A
Inductive extinction Yes; L+ -(55 to 60 V)
Digital input control Yes
Cable lengths
• Unshielded
• Shielded
600 m
1000 m
Data for the Analog Output
Resolution (including overrange) ± 10 V/13 bits + sign
Settling time
• For resistive load
• For capacitive load
• For inductive load
0.1 ms
0.5 ms
0.5 ms
Length of cable
• Shielded
Max. 100 m
Suppression of interference, limits of error
Operational limit (in the entire temperature range,
with reference to the output range)
± 0.4 %
Basic error limit (operational limit at 25°C with
reference to output range)
± 0.2 %
Temperature error (with reference to the output
range)
± 0.01 %/K
Linearity error (with reference to the output range) ± 0.02 %
Repeatability (in settled state at 25 °C, with
reference to the output range)
± 0.05 %
Output ripple (with reference to output range,
bandwidth 0 to 50 kHz)
± 0.02 %