EasyManua.ls Logo

Siemens SIMATIC ET 200S - Page 377

Siemens SIMATIC ET 200S
382 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1PosUniversal/Digital
7.10 Technical specifications
ET 200S Positioning
Operating Instructions, 05/2007, A5E00124871-04
377
Technical specifications 1PosU
Output current
0 signal (leakage current)
1 signal
Rated value
Permitted range
≤ 0.3 mA
0.5 A
7 mA to 0.6 A
Switch rate
Resistive load
Inductive load
Lamp load
100 Hz
2 Hz
≤ 10 Hz
Lamp load ≤5 W
Output delay (resistive load, output current 0.5 A)
At 0 to 1
At 1 to 0
typ. 150 µs
typ. 150 µs
Short-circuit protection of the output Yes
Threshold on 0.7 A to 1.8 A
Inductive extinction Yes; L+ -(55 to 60 V)
Digital input control Yes
Cable lengths
Unshielded
Shielded
600 m
1000 m
Encoder Connection at Incremental Encoders with 5 V Differential Signals
Level To RS 422
Terminating resistance 330 Ω
Differential input voltage Min. 1 V
Max. frequency 500 kHz
Galvanic isolation from ET200S bus Yes
Length of cable:
Shielded
Max. 50 m
Encoder Connection at Incremental Encoders with 24 V Signals
Galvanic isolation from ET200S bus Yes
Max. frequency 100 kHz
Length of cable shielded Max. 50 m
Input voltage
Rated value
0 signal
1 signal
DC24V
-30 to 5V
11V to 30V
Input current
0 signal
1 signal
≤ 2mA (bias current)
9 mA (typ.)
Connection of a two-wire BERO Type 2 Yes
Input characteristic curve To IEC 1131, Part 2, Type 2