EasyManua.ls Logo

Siemens SIMATIC ET 200S - Wiring and Fitting

Siemens SIMATIC ET 200S
382 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1STEP 5V/204kHz
2.8 Feedback and Control Interface
ET 200S Positioning
46 Operating Instructions, 05/2007, A5E00124871-04
Notes on the Feedback Bits
Feedback Bits Notes
DIS_NEG Shows whether the residual distance is negative when the positioning job is stopped during
acceleration. More pulses were emitted during this positioning job than were defined.
ERR_JOB This bit is set if the job is not clear or not possible.
Possible causes of error during a positioning job are as follows:
More than one control bit is set (DIR_P, DIR_M, C_PAR)
Start incremental mode, relative with DIR_P set at LIMIT_P
Start incremental mode, relative with DIR_M set at LIMIT_M
Start, although the STOP bit is set
Start, although external STOP is present
Start, although pulse enable is missing
Start, although multiplier G for velocity = 0
Start with STOP_REF_EN set, if REF digital input is set
Start with diagnostic error present
The mode is not known
The distance is 0 or larger than 1 048 575 (only for incremental mode)
A requested start was interrupted by CPU-Master-STOP
Possible causes of error during a parameter assignment request are as follows:
More than one control bit is set (DIR_P, DIR_M, C_PAR)
The multiplier n = 0 for the start-stop frequency
The multiplier i = 0 for acceleration/delay
ERR_PARA Incorrect parameter assignment for the ET 200S station.
Cause: Multiplier n of the start-stop frequency = 0 or the multiplier i for acceleration/delay = 0.
The parameter error bit is deleted when a correct parameter assignment is transmitted.
ERR_24V The sensor supply was short-circuited and is now switched off. ERR_24V is reset if it was
acknowledged with the EXTF_ACK control bit. After the short circuit has been eliminated, the sensor
supply is switched on again and ERR_24V remains deleted.
POS Positioning is in operation: This bit is set during incremental mode or a search for reference.
POS_RCD POS_RCD is deleted at the start of an incremental run or a search for reference. After a correct run,
the residual distance = 0, that is, the defined position is reached and POS_RCD is thus set.
If the run was interrupted (if the stepping motor stops or the pulse enable is deleted), POS_RCD
remains deleted.
Residual distance A 20-bit value that contains the pulses that still have to be traversed (without signs).
STOP_EXT Cause of STOP: External STOP
STOP_LIMIT_M Cause of STOP: Limit switch reached LIMIT_M
STOP_LIMIT_P Cause of STOP: Limit switch reached LIMIT_P
STOP_REF Cause of STOP: Reference cam reached
STS_DI The bit displays the status of the DI 3 digital input.
STS_DRV_EN This bit is set when one of the following occurs, depending on the assigned parameter function of the
digital input:
The external pulse enable is set.
The DRV_EN control bit is set for the pulse enable.
STS_JOB This bit is set as a feedback message when a job request for a positioning or parameter assignment
job is detected and then reset when the job has been executed.
STS_REF The bit displays the status of the REF digital input.

Table of Contents

Other manuals for Siemens SIMATIC ET 200S

Related product manuals