EasyManuals Logo

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO User Manual

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO
193 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #181 background imageLoading...
Page #181 background image
10 Dealing with Problems / Error Displays
181
IE/ASINTERFACE LINK PN IO as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000G8976C21603
Table 10-2 Error/fault displays of the LEDs for the AS-i line (bottom right)
“LED” / Fault/error RemedyPossible Cause
After failure of an AS-i slave,
“AUP” remains off.
IE/AS-i LINK is in configuration
mode.
”Automatic Address Program-
ming” is not possible in configura-
tion mode.
Program the address of the new
AS-i slave with the address pro-
grammer or using the data record
interface of the IE/AS-i LINK.
More than one AS-i slave has fai-
led.
Check the AS-i cable.
If “APF” is displayed at the same
time, check the power supply on
the AS-i cable.
If more than one slave is defec-
tive, program the address on the
replaced slaves using the addres-
sing unit.
The IE/AS-i LINK has detected
unconfigured AS-i slaves.
Remove the unconfigured AS-i
slaves from the AS-i cable.
Automatic address programming
does not work although “AUP”
was previously lit.
The configuration data (I/O confi-
guration, ID code) of the replaced
AS-i slave do not match the va-
lues of the original slave.
Check whether the correct “repla-
cement slave” was used.
Compare the information from the
manufacturer about configuration
data.
If you want to replace the original
slave with a different type, assign
the address with the addressing
unit and reconfigure the IE/AS-i
LINK.
The replaced AS-i slave does not
have the address “0”.
Address the replaced slave at ad-
dress 0 or the correct target ad-
dress. (for example with the dis-
play).
The replaced AS-i slave is not cor-
rectly connected or is defective.
Check the connections of the
slave and if necessary replace the
slave.
The IE/AS-i LINK does not switch
from configuration mode to protec-
ted mode (”CM” not lit).
An AS-i slave with address 0 is
connected to the AS-i cable.
IE/AS-i LINK cannot switch to the
protected mode as long as this
slave exists.
Remove the AS-i slave with ad-
dress 0.
-

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO and is the answer not in the manual?

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET IE/AS-INTERFACE LINK PN IO
CategoryControl Unit
LanguageEnglish

Related product manuals