Parameter ID Unit Default Min Max Description
Rated output
current
2040 A 100.0 12.0 1500.0 Rated drive output current RMS. Set equal to the cell
output current rating.
Note: Size the output Hall eects and burden resis‐
tors for the cell current rating.
Hall Eects
Voltage
2041 V 24 The required voltage of the drive's hall eect trans‐
ducers. Possible options are:
• 15 V
• 24 V
Rated Leading Vars 2042 % 50.0 0.0 75.0 Rated leading VAR output in percent of rated input
transformer VA.
Rated Lagging Vars 2043 % 50.0 0.0 75.0 Rated lagging VAR output in percent of rated input
transformer VA.
Control loop type 2050 OLVC Select control loop algorithm type
1
:
• V/Hz for parallel motors.
• OLVC for single induction motors.
• CLVC for single induction motors with speed sen‐
sor(s).
• OLTM for checking cell modulation and testing
Hall eect transducer only. Not intended for con‐
tinuous motor or load control.
• SMC without speed sensor.
• CSMC with speed sensor.
• SMDC which automatically sets high starting tor‐
que.
• PMM.
Parallel system 2051 Disable Enable parallel drive control operation.
Drives/motor wind‐
ing
2052 1 1 99 Number of drives connected to a single motor.
Number of windings 2053 1 1 99 Number of sets of motor windings.
Drive index 2054 0 0 255 Drive sequence number determined by PLC.
Service Mode 2056 0 0 99999 Service mode register.
PMM Control 2980 Menu for PMM control.
* Rated input current calculation is derived as follows:
Rated Input Current = [(kVA rating) x (802)] ÷ [(√3) x (rated nominal primary voltage)
x (0.96) x (0.94)
= [(kVA rating) ÷ (rated nominal primary voltage)] x 513.11
1
Changing the control loop algorithm type to OLTM or V/Hz disables fast bypass (2600) and
spinning load (2430) regardless of parameter setting.
Parameter Assignment/Addressing
6.5 Options for Drive Menu (2) - rst part
NXGPro+ Control Manual
102 Operating Manual, A5E50491925A