Table 6-8 Drive Parameter Menu (2000) Parameters
Parameter ID Unit Default Min Max Description
Rated input
voltage
2010 V 4160 200 125000 Rated RMS input voltage to the drive. Set according to
the input transformer primary voltage rating.
Note: The input attenuator kit must correspond to
the rated primary voltage of the transformer.
Rated input
current
2020 A 100.0 12.0 3000.0 Rated RMS input current to the drive. Set according to
input transformer nameplate kVA rating as noted be‐
low.*
Rated secondary
power
2022 kVA 100 100 50000 Nameplate power rating of transformer secondary
power in kVA
For air-cooled transformers:
1. Check the transformer Rating Plate for the trans‐
former rated power.
2. Check to see if there is the following text on the
transformer Rating Plate… “kVA sum of seconda‐
ries rated at _ _ _ _ kVA”.
3. Take the larger of the two values as the trans‐
former secondary power.
For water-cooled transformers:
1. If the transformer secondary kVA value is listed
use this value.
2. If the transformer secondary kVA is not listed use
the listed transformer kVA.
Note: For NXGpro version 6.3, this parameter has a
xed value of 50000. This value is enforced with a
default and maximum value of 50000. The mini‐
mum value is set at 49995. The drive will operate
properly as with all previous software versions. This
xed value has the eect of disabling the secondary
rollback function.
Harmonic load factor 2024 1.12 1 1.25 Harmonic loading factor from transformer design en‐
gineer specication. Refer to the section of this man‐
ual "Protecting Transformer by Limiting Secondary
Currents".
Rated output voltage 2030 V 4160 200 23000 Rated drive output voltage RMS. Set according to the
rating of the output attenuator kit.
Note: This value is typically equal to or higher than
the motor voltage rating.
Parameter Assignment/Addressing
6.5 Options for Drive Menu (2) - rst part
NXGPro+ Control Manual
Operating Manual, A5E50491925A 101