10.10 Selecting the active SOP
It is possible to store multiple system programs on the 󹪞ash card. The purpose is for factory
testing or commissioning, as the SOP allows the drive to be run with minimal external
connections.
Note
Requirement when selecting the active SOP
To select a di󹪜erent active SOP, the drive must not be running.
This could cause drive instability and/or a trip.
Use the parameter Select system program (9146) to select from a pick list of all available SOPs.
To determine the SOP that is currently selected, use the Display sys prog name (9140) function.
Find both parameters under the SOP and Serial Functions Menu (9110).
Operating the Software
10.10 Selecting the active SOP
NXGPro+ Control Manual
440 Operating Manual, A5E50491925A