3.3 Control Overview
SINAMICS Perfect Harmony™ GH180 drives maintain a simple "synchronous" control. It
coordinates the complex, cell-based power topology to produce a simple, multi-level pulse
width modulation (PWM) to the output connection of the drive. Basic operation is summarized
as follows:
1. The control sends a message to each power cell control via dedicated 󹪝ber links. The return
cell response, via a separate 󹪝ber, communicates cell status and diagnostics.
2. The cell executes the request by gating one switch pair, which results in one of the following
outcomes:
Plus DC voltage
Minus DC voltage
Zero voltage
3. The cell control con󹪝rms that the switch pair gated.
4. The control con󹪝rms gating from:
Output voltage divider
Output Hall e󹪜ect current transducer
No two cells switch at the same time.
The cell switching rate is low compared to the e󹪜ective switching frequency of the VFD:
Typically 600 Hz carrier frequency per pole results in 1200 Hz switching frequency per cell.
The VFD e󹪜ective switching frequency is calculated simply as:
cell switching frequency * number of cells per phase
The switching rate is constant over the entire output frequency range.
The default control mode is open loop vector control (OLVC). Control modes Volts/Hertz (V/
Hz), closed loop vector control (CLVC) with encoder, and permanent magnet motor (PMM)
control without encoder are also available.
Control Description
3.3 Control Overview
NXGPro+ Control Manual
Operating Manual, A5E50491925A 35