6.3 Options for Motor Menu (1) - rst half
Note
Changing Drive Parameters
Only Siemens trained personnel are authorized to change drive parameters.
Familiarize yourself with the safety notes in Section Safety Notes for Parameter Changes and
preferentially contact Siemens customer service before changing the default conguration.
The Motor Menu (1) consists of the following menu options:
• Motor Parameter Menu (1000)
• Limits Menu (1120)
• Speed Derate Curve Menu (1151)
• Auto-tune Menu (1250)
• Encoder Menu (1280)
• Current Prole Menu (1092)
These menus are explained in the tables that follow.
Table 6-2 Motor Parameter Menu (1000) Parameters
Parameter ID Unit Default Min Max Description
Motor frequency 1020 Hz 60.0 15.0 400.0 Enter the rated or base frequency of the mo‐
tor from the nameplate.
Full load speed 1030 RPM 1780 1 31500 Enter the full load speed of the motor from
the nameplate. Full load speed is base or
rated speed minus slip.
Motor voltage 1040 V 4160 380 13800 Enter the rated voltage for the motor from
the nameplate.
Full load current 1050 A 125.0 12.0 1500.0 Enter the rated nameplate full load current
of the motor.
No load current 1060 % 25.0 0.0 100.0 Enter the no load current of the motor from
the nameplate, if it is provided, or use the
default value. Use of auto-tune stage 2 is
NOT recommended except in special circum‐
stances. See note in auto-tune description.
Mag current thresh 1061 % 80.0 50.0 100.0 Threshold of reactive current needed to
magnetize before a 'Failed to Magnetize'
fault occurs.
Motor kW rating 1010 kW 746.0 90.0 100000.0 Enter the motor kW (0.746 * Hp) from the
nameplate.
Leakage induc‐
tance
1070 % 16.0 0.0 30.0 Enter the motor leakage inductance based
on percent of drive base impedance if provi‐
ded on nameplate or motor sheet, or calcu‐
late using auto-tune stage 1.
Parameter Assignment/Addressing
6.3 Options for Motor Menu (1) - rst half
NXGPro+ Control Manual
90 Operating Manual, A5E50491925A