EasyManua.ls Logo

Siemens SINAMICS PERFECT HARMONY GH180 - Options for Multiple Configuration Files

Siemens SINAMICS PERFECT HARMONY GH180
538 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.19 Options for Multiple Con󹪝guration Files
The drive can operate with multiple motors that may vary in size. The drive uses multiple
parameter con󹪝guration 󹪝les to accomplish multiple motor operation. There is one master
con󹪝guration 󹪝le that is always named current cfg. The slave 󹪝les are stored on the
CompactFlash card in a subfolder of the 'CfgFiles' con󹪝guration folder named 'SubCfgs'. The
slave 󹪝les can have any legal name conforming to the "xxxxxxxx.yyy" 󹪝le naming convention.
File extension for slave con󹪝guration 󹪝les
The 󹪝le extension of slave con󹪝guration 󹪝les is always ‘.sfg’. You cannot add or change the 󹪝le
extension for the slave con󹪝guration 󹪝les through the menus. Choose 8 characters only for the
󹪝le name.
Press [ENTER] to save the parameters as they exist in memory to a new con󹪝guration 󹪝le name.
This 󹪝le will be stored to the CompactFlash card in the ‘SubCfgssubdirectory. This function does
not make this con󹪝guration 󹪝le the active con󹪝guration 󹪝le. It uses the current data in memory
to create a new slave con󹪝guration 󹪝le. Any parameter that is saved to a slave con󹪝guration 󹪝le is
identi󹪝able by the small ‘s’ adjacent to the parameter ID number if it has not been changed from
the default setting, or a ‘$’ if it has been changed from the default setting, for example (s9586)
or ($9586).
Creating con󹪝guration 󹪝les
You can create con󹪝guration 󹪝les at runtime in the drive’s memory and then store them to the
CompactFlash card.
Create slave 󹪝les via the keypad menus. To do so, set the slave parameters as desired and write
them to the CompactFlash card, see Table Slave Setup and Con󹪝guration Parameters.
You may set up to 8 SOP 󹪞ags to point to a con󹪝guration 󹪝le. Use the menus to map each SOP
󹪞ag to a corresponding con󹪝guration 󹪝le. Once mapped, use the SOP 󹪞ags to activate the SOP
for a particular motor.
Menu Item Descriptions
Multiple con󹪝g 󹪝les Use this pick list to switch slave con󹪝guration 󹪝les.
Disable this item by setting it to "OFF". No other multiple con󹪝guration
󹪝le menus will be displayed.
Enable this item by setting any one of the SOP 󹪞ags to true. The cor‐
responding con󹪝guration 󹪝le will become active.
Show active con󹪝g 󹪝le Use this function to display the current active con󹪝guration 󹪝le.
Only one con󹪝guration 󹪝le can be active at one time.
If the correct con󹪝guration 󹪝le is not displayed, check the SOP 󹪝le for
accuracy. Check the ‘Setup SOP con󹪝guration 󹪞ags menu' to be sure
the correct 󹪝le is mapped to the SOP 󹪞ag.
Parameter Assignment/Addressing
6.19 Options for Multiple Con󹪝guration Files
NXGPro+ Control Manual
Operating Manual, A5E50491925A 171