Direct Optically Isolated Connection
The optically isolated interface provided by Siemens is per the "Encoder Block Diagram" as shown
below.
(1&2'(5
)XUQLVKHG,QVWDOOHG
E\&XVWRPHU
(1;075
0,&52125
)XUQLVKHGE\6,(0(16
DVSQ$(
,QVWDOOHGE\&XVWRPHU
32:(56833/<
)XUQLVKHG,QVWDOOHG
E\&XVWRPHU
),%(5237,&&$%/(
)XULVKHG,QVWDOOHGE\
&XVWRPHU
673&&RQQHFWRUV
20
mP*UDGHG,QGH[00)
/LQNGLVWDQFHOHVVHURIG%RUNP
(15&95
0,&52125
)XUQLVKHGE\6,(0(16
DVSQ$(
LQWKH'ULYH
),%(5237,&
673&
&211(&7,21
),%(5237,&
673&
&211(&7,21
9'&
P$(1&2'(532:(5
Figure 5-3 Encoder Block Diagram (showing optically isolated interface)
5.3.4 User Inputs and Outputs
The drive provides terminal strips as required for end-user connection of analog and digital input/
output (I/O) signals to the drive. Speci󹪝c I/O implementation is customized for each drive and you
must refer to the drawings provided with the drive. The control interfaces each of these I/O
points via 󹪝ber optic connected user I/O boards or RS232 connected WAGO expansion I/O
modules (or both). Up to four 󹪝ber optically connected user I/O boards may be connected in
linear series for greater capabilities. The 󹪝rst board in the series is always dedicated to I/O points
critical to the drive operation. The other expansion I/O connections, as required, are intended for
user to system I/O that is for typical drive operation or non-critical for protection.
In de󹪝ning the I/O, the I/O points associated with the user I/O board(s) are referred to as internal
I/O and the WAGO is referred to as external I/O.
The system operating program (SOP) determines the routing of signals to each of these I/O
points, while the control provides a means to de󹪝ne the signal, the type and the scaling of the
analog signals.
5.3.5 User I/O Board
Typically an NXGpro control system has a 󹪝ber optic connected user I/O board for system
interconnections. The 󹪝rst board is always used for the critical I/O of the system. Refer to
Section Dedicated I/O for the mapping of these I/O.
The control system can support up to three additional user I/O boards via 󹪝ber optic
communication. The boards may be remotely located up to 35 meters in 󹪝ber length. Available
boards support either all 24 V or all 120 V on their digital inputs. The digital inputs cannot be
Hardware User Interface Description
5.3 User Accessible Interfaces
NXGPro+ Control Manual
Operating Manual, A5E50491925A 71