Table 6-32 Internal Analog Input 8 Menu (2711) Parameters
Parameter ID Unit Default Min Max Description
Type 2712 1 Set the operational mode for internal AI8:
• 0 to 20 mA
• 4 to 20 mA
• 0 to 10 V
• RTD
Hardware Zero 2713 0 -200 200 Internal analog input 8 zero
Hardware Span 2714 1 0.75 1.25 Internal analog input 8 span
RTD Alpha Value 2105 0.39 0.1 0.7 Set the internal I/O RTD's analog input alpha
value.
Table 6-33 Internal Analog Input 9 Menu (2715) Parameters
Parameter ID Unit Default Min Max Description
Type 2716 1 Set the operational mode for internal AI9:
• 0 to 20 mA
• 4 to 20 mA
• 0 to 10 V
• RTD
Hardware Zero 2717 0 -200 200 Internal analog input 9 zero
Hardware Span 2718 1 0.75 1.25 Internal analog input 9 span
RTD Alpha Value 2106 0.39 0.1 0.7 Set the internal I/O RTD's analog input alpha
value.
Table 6-34 Internal Analog Input 10 Menu (2721) Parameters
Parameter ID Unit Default Min Max Description
Type 2722 1 Set the operational mode for internal AI10:
• 0 to 20 mA
• 4 to 20 mA
Hardware Zero 2723 0 -200 200 Internal analog input 10 zero
Hardware Span 2724 1 0.75 1.25 Internal analog input 10 span
Parameter Assignment/Addressing
6.6 Options for Drive Menu (2) - second part
NXGPro+ Control Manual
118 Operating Manual, A5E50491925A