10.9 Multiple Conguration Files
The control allows for the use of up to eight separate conguration les. This is to allow for use
of the drive with up to eight separate, non-identical motors. These les contain most of the
parameters of the drive, all motor parameters and most loop tuning parameters are contained
in these les.
To use multiple conguration les, enable parameter Multiple cong les (9185) in the SOP &
Serial Functions Menu. The default is o. The associated submenu is Setup SOP cong ags
(9186) where slave les can be created and assigned to the SOP variables via the menu items.
Refer to Section Options for Multiple Conguration Files in Chapter Parameter Assignment/
Addressing for information on creating and programming the slave les.
Once the les are created and enabled, they are selected via the eight SOP ags
SOPConfigFile1_O to SOPConfigFile8_O in the logic of the SOP le. Ensure that only one
valid ag is set true at a time within the SOP.
CAUTION
Potential Drive Instability or Trip
Switching SOP ags could cause drive instability and/or a trip.
Do not switch SOP ags while the drive is running.
Since the conguration les can also be changed via the menu, there is a potential conict that
could arise between whether the menu or the SOP selected le is to be used. If the menu is used
to override the SOP selection, then the menu selection becomes the active conguration. This
will remain in eect until the SOP changes the conguration le to be dierent from the menu
selection.
Operating the Software
10.9 Multiple Conguration Files
NXGPro+ Control Manual