7.14 Data Loggers
7.14.1 Data Logs
The control includes three separate data loggers to record events detected by the software. The
logs are stored in non-volatile memory and you can capture data via the VFD’s USB ports or the
ethernet port.
USB port: Use by inserting a USB disk drive. Logs are saved in the root directory of the
attached USB drive.
Ethernet port: You must connect a PC, running the NXGpro ToolSuite software, to the drive
and upload the 󹪝les directly from the PC. Refer to the NXGpro ToolSuite Software Manual for
operational information.
7.14.2 Event Log
The event log is a very large circular 󹪝le that is used to record signi󹪝cant drive events. Recorded
data is time stamped to a resolution of 1 millisecond. Data in the log includes:
All alarms and faults, i.e. alarm/fault log data.
All parameter changes.
If enabled, the historic log at the time of a fault in a truncated form, to prevent event log
over󹪞ow.
Signi󹪝cant events:
CPU bootup including installed NXGpro software version.
Medium voltage status.
Drive operating state changes, e.g. idle, magnetize, run, stop.
Precharge state changes
Fault reset requests.
Complete pre-charge sequence including success, all states and faults.
Refer to Event Log Menu (6180) in Section Options for Log Control Menu (6) of Chapter
Parameter Assignment / Addressing for associated parameters.
7.14.3 Alarm/Fault Log
The alarm/fault log consists of a circular bu󹪜er that records up to 256 faults or alarms, so that you
can access the 256 most recent faults and/or alarms that have been detected. The faults and/or
alarms are time stamped to a resolution of 1 second, and also include a time stamp showing
when the fault and/or alarm was reset or cleared.
Refer to Alarm/Fault Log Menu (6210) in Section Options for Log Control Menu (6) of Chapter
Parameter Assignment / Addressing for associated parameters.