Table 6-28 Internal Analog Input 4 Menu (2689) Parameters
Parameter ID Unit Default Min Max Description
Type 2690 1 Set the operational mode for internal AI4:
• 0 to 20 mA
• 4 to 20 mA
Hardware Zero 2691 0 -200 200 Internal analog input 4 zero
Hardware Span 2692 1 0.75 1.25 Internal analog input 4 span
Table 6-29 Internal Analog Input 5 Menu (2693) Parameters
Parameter ID Unit Default Min Max Description
Type 2694 1 Set the operational mode for internal AI5:
• 0 to 20 mA
• 4 to 20 mA
• 0 to 10 V
• RTD
Hardware Zero 2695 0 -200 200 Internal analog input 5 zero
Hardware Span 2696 1 0.75 1.25 Internal analog input 5 span
RTD Alpha Value 2103 0.39 0.1 0.7 Set the internal I/O RTD's analog input alpha
value.
Table 6-30 Internal Analog Input 6 Menu (2701) Parameters
Parameter ID Unit Default Min Max Description
Type 2702 1 Set the operational mode for internal AI6:
• 0 to 20 mA
• 4 to 20 mA
• 0 to 10 V
• RTD
Hardware Zero 2703 0 -200 200 Internal analog input 6 zero
Hardware Span 2704 1 0.75 1.25 Internal analog input 6 span
RTD Alpha Value 2104 0.39 0.1 0.7 Set the internal I/O RTD's analog input alpha
value.
Table 6-31 Internal Analog Input 7 Menu (2705) Parameters
Parameter ID Unit Default Min Max Description
Type 2706 1 Set the operational mode for internal AI7:
• 0 to 20 mA
• 4 to 20 mA
Hardware Zero 2707 0 -200 200 Internal analog input 7 zero
Hardware Span 2708 1 0.75 1.25 Internal analog input 7 span
Parameter Assignment/Addressing
6.6 Options for Drive Menu (2) - second part
NXGPro+ Control Manual
Operating Manual, A5E50491925A 117