The following functions performed by the SIB provide a signal directly to the modulator to shut
down all cell switching immediately:
Inhibit or CR3 signal to modulator. Refer to Section Inhibit Input (Control Relay 3, CR3).
5.2.2 Test Point Port
The NXGPro+ Control has a dedicated test port for safe measurement of critical feedback signals.
A DIN41612 type connector is available on the main control board for breaking out the various
analog feedback signals to test points. The analog feedback signals do not have test points on
the main control board and are only available through this connector. In addition to the analog
signals, select FPGA signals are brought out as test points. The DIN41612 type connector allows
for either the use of a test point board or an automated data collection system to directly monitor
the analog feedback signals.
NOTICE
Risk of damage to equipment.
Do not attempt direct manual measurement of signals at the port connector.
This can cause damage to components.
Instead always directly measure signals via the test point board.
For correct use of the signals beyond the test point board, consult the design documentation for
proper scaling. Refer to the table below for details of the available signals.
Table 5-1 NXGPro+Test Port Signals: Connector Pins (P5)
Quantity Name Description Pin Number Scaling at Break‐
out Board
3 VIA, VIB, VIC Phase A, B and C input voltage 1 A3; B5; A2 5.3864 Vpeak
3 VIA2, VIB2, VIC2 Phase A, B and C input voltage 2 B2; B3; B4 5.3864 Vpeak
2 IIB, IIC Phase B and C input current A5; A4 5.0 Vpeak
3 VMA, VMB, VMC Phase A, B and C motor voltage A12; A13; A14 5.3864 Vpeak
3 IMA, IMB, IMC Phase A, B and C motor current A7; A8; A9 5.00 Vp-p
1 VCMV Common mode motor voltage C1 5.3864 Vpeak
3 IFA, IFB, IFC Phase A, B and C 󹪝lter current B7; B8; B9 5.0 Vpeak
3 VMAI1, VMB1, VMCI1 Phase A, B and C
Integrated motor voltage: low speed
B11; B13; B15 ~ 3.8 Vrms at
100 % speed 60 Hz
3 VMA22, VMB22, VMC22 Phase A, B and C
Integrated motor voltage: high speed
B10; B12; B14 TBD
2 Encoder A, B opto-couple input C13; C14 3.3 V logic
1 IOC Instantaneous over current A10 3-ph IM
1 IOC REF Instantaneous over current - reference C3 0 to 3.3 V range
1 Inhibit C2 3.3 V high = inhibit
1 VON Output Neutral Voltage C4 3.8Vrms at 100%
speed 60Hz