Table 6-12 Speed Ramp Setup Menu (2260) Parameters
Parameter ID Unit Default Min Max Description
Accel time 1 2270 sec 5.0 0.0 3200.0 Acceleration time 1 in seconds from zero to
rated speed.
Decel time 1 2280 sec 5.0 0.0 3200.0 Deceleration time 1 in seconds from rated to
zero speed.
Accel time 2 2290 sec 5.0 0.0 3200.0 Acceleration time 2 in seconds from zero to
rated speed.
Decel time 2 2300 sec 5.0 0.0 3200.0 Deceleration time 2 in seconds from rated to
zero speed.
Accel time 3 2310 sec 5.0 0.0 3200.0 Acceleration time 3 in seconds from zero to
rated speed.
Decel time 3 2320 sec 5.0 0.0 3200.0 Deceleration time 3 in seconds from rated to
zero speed.
Jerk rate 2330 0.1 0.0 3200.0 Jerk rate in time to reach an acceleration rate
that will achieve rated velocity in 1 sec.
Table 6-13 Critical Frequency Menu (2340) Parameters
Parameter ID Unit Default Min Max Description
Skip center freq 1 2350 Hz 15.0 0.0 360.0 Enter the center of the 󹪝rst critical frequency
band to be avoided.
Skip center freq 2 2360 Hz 30.0 0.0 360.0 Enter the center of the second critical fre‐
quency band to be avoided.
Skip center freq 3 2370 Hz 45.0 0.0 360.0 Enter the center of the third critical frequen‐
cy band to be avoided.
Skip bandwidth
1
2380 Hz 0.0 0.0 6.0 Enter the bandwidth of the 󹪝rst critical fre‐
quency band to be avoided.
Skip bandwidth
2
2390 Hz 0.0 0.0 6.0 Enter the bandwidth of the second critical
frequency band to be avoided.
Skip bandwidth
3
2400 Hz 0.0 0.0 6.0 Enter the bandwidth of the third critical fre‐
quency band to be avoided.
Table 6-14 Spinning Load Menu (2420) Parameters
Parameter ID Unit Default Min Max Description
Spinning load
mode*
2430 O󹪜 Enable or disable spinning load and set the
direction of frequency scans:
O󹪜
Forward
Reverse
Both; scans 󹪝rst in the forward direction,
then in the reverse direction.
Scan end thresh‐
old
2440 % 20.0 1.0 50.0 The point where scan ends if motor 󹪞ux is
above this level, as a percentage of motor
rated 󹪞ux.