Parameter ID Unit Default Min Max Description
Current Level
Setpoint
2450 % 15.0 1.0 50.0 Set the drive current level (I
d
), as a percent‐
age of motor rated current, used during
scanning.
Current ramp 2460 sec 0.01 0.00 5.00 Time to ramp drive current (I
d
) to Current
Level Setpoint.
Max current 2470 % 50.0 1.0 50.0 Set the current trip level to abort spinning
load, as a percentage of motor rated current,
for scanning. Use the default value of 50 %.
Frequency scan
rate
2480 sec 3.00 0.00 5.00 Set the time taken to scan from rated speed
to zero. The default value of 3.00 sec is usu‐
ally satisfactory.
* If spinning load mode is disabled from this parameter, it will enable automatically on an as-
needed basis; this occurs only when fast bypass is enabled and only for the duration of the
bypass. This action is internal and does not require user intervention. This action does not
a󹪜ect the spinning load mode paramete.
Table 6-15 Conditional Timer Setup Menu (2490) Parameters
Parameter ID Unit Default Min Max Description
Cond stop timer 2500 sec 0.8 0.0 999.9 Dwell time after stop is invoked. User function de‐
󹪝ned.
Not implemented
Cond run timer 2510 sec 0.8 0.0 999.9 Dwell time after start is invoked. User function de‐
󹪝ned.
Not implemented
Table 6-16 Cell Menu (2520) Parameters
Parameter ID Unit De‐
fault
Min Max Description
Installed cells/
phase
2530 4 1 8 Number of installed cells per phase in the drive.
Permitted min cell
count
2541 12 3 24 Set the permitted minimum cell count which establishes
the maximum number of cells that may be bypassed. At
least one cell must be operable in each phase.
A further restriction is enforced in the code to only allow
a maximum of nine cells in bypass. A bypass fault will
occur if the bypass operation attempts to exceed the
number.