Parameter ID Unit Default Min Max Description
AFE cell DC P gain 2587 1.24 0.5 3.3 Set the AFE cell DC control proportional con‐
stant.
AP cell DC I gain 2588 4.8435 1 10 Set the AP cell DC control integral constant.
AP cell Id P gain 2589 0.2187 0.0078 4 Set the AP cell real current regulator propor‐
tional constant.
AP cell Id I gain 2591 46.875 5.859 3000 Set the AP cell real current regulator integral
constant.
AP cell Id D gain 2592 x100 0.0166 0 0.0333 Set the AP cell real current regulator deriva‐
tive constant.
AP cell Iq P gain 2593 0.2187 0.0078 4 Set the AP cell reactive current regulator pro‐
portional constant.
AP cell Iq I gain 2594 46.875 5.859 3000 Set the AP cell reactive current regulator in‐
tegral constant.
AP cell Iq D gain 2595 x100 0.0166 0 0.0333 Set the AP cell reactive current regulator de‐
rivative constant.
AP di󹪜 temp fault lvl 2596 deg 24.0 10.0 30.0 Set the AP cell maximum temperature di󹪜er‐
ential before fault.
AP Mplx Data Select 2597 Air Temp Select the source of the AP cell multiplexed
data.
AP sync ang o󹪜set 2579 deg 0 -180 180 Set the AP cell carrier synchronous angle o󹪜‐
set for all cells. Use to o󹪜set drive carriers
among two or more drives.
Set Angles 2598 Set the AP cell angles as they relate to the
primary voltage.
AP cell ang o󹪜 1 2571 deg -181 -181 180 Set the AP cell angle o󹪜set from the trans‐
former primary voltage for this rank.*
AP cell ang o󹪜 2 2572 deg -181 -181 180 Set the AP cell angle o󹪜set from the trans‐
former primary voltage for this rank.*
AP cell ang o󹪜 3 2573 deg -181 -181 180 Set the AP cell angle o󹪜set from the trans‐
former primary voltage for this rank.*
AP cell ang o󹪜 4 2574 deg -181 -181 180 Set the AP cell angle o󹪜set from the trans‐
former primary voltage for this rank.*
AP cell ang o󹪜 5 2575 deg -181 -181 180 Set the AP cell angle o󹪜set from the trans‐
former primary voltage for this rank.*
AP cell ang o󹪜 6 2576 deg -181 -181 180 Set the AP cell angle o󹪜set from the trans‐
former primary voltage for this rank.*
AP cell ang o󹪜 7 2577 deg -181 -181 180 Set the AP cell angle o󹪜set from the trans‐
former primary voltage for this rank.*
AP cell ang o󹪜 8 2578 deg -181 -181 180 Set the AP cell angle o󹪜set from the trans‐
former primary voltage for this rank.*
Regen OV I gain 2623 0.0010 0.0001 1.0000 Set the regen overvoltage rollback regulator
integral gain.
1
Regen OV P gain 2624 0.0000 0.0000 10.0000 Set the regen overvoltage rollback regulator
proportional gain.
1
Parameter Assignment/Addressing
6.5 Options for Drive Menu (2) - 󹪝rst part
NXGPro+ Control Manual
110 Operating Manual, A5E50491925A