Parameter ID Unit Default Min Max Description
Sampling Delay
Comp
3570 % 0.0 0.0 150.0 Compensate the 󹪞ux vector angle for sampling
delay on high speed motor operation.
Carrier frequency 3580 Hz 600.0 100.0 1550.0 Enter the IGBT switching frequency. The control
adjusts the entered value according to available
resolution from the modulator registers, e.g., if
you enter 400.0, the actual frequency may be
398.6:
f
C
= Power cell carrier frequency
f
O
= Drive rated output frequency
For f
O
< 167 Hz, f
C
= 600 Hz is typically adequate.
A smaller value of f
C
can be chosen provided
300 Hz < f
C
> (3.6 x f
O
) Hz.
For f
O
= 167 to 330 Hz, 1550 Hz > f
C
> (3.6 x f
O
) Hz.
High switching frequencies may result in some
derating due to increased switching losses. Con‐
sult Siemens customer service for derating values.
Table 6-50 Input Processing Menu (3000) Parameters
Parameter ID Unit Default Min Max Description
PLL prop gain 3010 70.0 0.0 200.0 Proportional gain of input phase-locked loop
(PLL).
PLL integral gain 3020 3840.0 0.0 12000.0 Integral gain of input PLL.
Input current scaler 3030 1.0 0.0 2.0 Set the scaling for input current feedback. Default
value is normally adequate.
CT secondary turns 3035 200 50 3000 Secondary side turns for input current CT, with
primary turns equal to 5.
Input voltage scaler 3040 1.0 0.0 2.0 Set the scaling for input line voltage feedback.
Default value is normally adequate.
PT secondary turns 3011 1 1 3000 Secondary turns input voltage PT.
VAR control 3041 Submenu Access the cell input control parameters.
Input Attenuator
Sum
3045 kOhm 3000 1 32767 Set scaling for input nominal value. This is the
sum of the two input resistors per phase.
CAUTION
PLL gains and scaling parameter values
Changing PLL gains from the default values or setting scaling parameter values incorrectly can
cause unintended results that a󹪜ect performance and disable drive protections.
Scaling parameter values must match actual hardware ratings.
Never change scaling parameter values from actual hardware ratings.
Parameter Assignment/Addressing
6.8 Options for Stability Menu (3) - 󹪝rst half
NXGPro+ Control Manual
126 Operating Manual, A5E50491925A