NOTICE
* NXGPro+ uses a standard driver and does not allow the installation of drivers, therefore some
USB disk devices may not be compatible with NXGPro+.
• When attempting to upload information using a USB disk drive, check the keypad display for
a failure message such as, "An error has occurred" or "Error opening output le".
• If the upload fails, change the brand or type of USB ash disk and retry.
• Refer to the section of this manual "USB ash disk requirements", "Known Issues with USB
ash disks", and "Keypad error messages" for more information on USB.
Table 6-87 Historic Log Menu (6250) Parameters
Parameter ID Default Description
Store in event log 6255 On When selected, the historic log is stored in the event log.
Historic log variable 1 6260 Spd Ref Select the 1st variable for the historic log.
1
Historic log variable 2 6270 Trq I Cmd Select the 2nd variable for the historic log.
1
Historic log variable 3 6280 Mtr Flux Select the 3rd variable for the historic log.
1
Historic log variable 4 6290 Pwr Out Select the 4th variable for the historic log.
1
Historic log variable 5 6300 I Total Out Select the 5th variable for the historic log.
1
Historic log variable 6 6310 Mag I Fdbk Select the 6th variable for the historic log.
1
Historic log variable 7 6320 Mtr Flux Select the 7th variable for the historic log.
1
Historic log upload 6330 Upload the historic log to a USB connected disk drive.
1
See Table Pick list variables for Historic Log for pick list variables.
Table 6-88 Pick list variables for Historic Log (all units are %)
Abbreviation Description
Mtr Spd Motor speed
Spd Ref Speed reference
Spd Dmd Raw speed demand
Trq I Cmd Torque current command
Trq I Fdbk Torque current feedback
Mag I Cmd Magnetizing current command
Mag I Fdbk Magnetizing current feedback
I Total Out Total motor current
Mtr Volt Motor voltage
Mtr Flux Motor ux
V Avail Line voltage available
V Avail RMS Line voltage RMS
Pwr Out Output power
V Neutral Output neutral volts
Parameter Assignment/Addressing
6.15 Options for Log Control Menu (6)
NXGPro+ Control Manual
156 Operating Manual, A5E50491925A