Parameter ID Unit Default Min Max Description
Ground Fault
Limit
7106 % 40.0 0.0 100.0 Set the level above which the drive issues
an input ground fault alarm.
Ground Fault
Time Const
7107 sec 0.2 0.001 2.0 Set the time constant of 󹪝lter used for
averaging input neutral voltage when de‐
tecting a ground fault.
Dedicated Input
Protect
7108 O󹪜 Input protection uses dedicated inputs
and outputs controlled by NXGpro code.
Options are:
O󹪜
On
Input Breaker
Open Time
7125 sec 0.4 0.02 0.5 Set the maximum expected opening time
for the input breaker. This value is used for
Tamper Resistant Input Protection.
Test IP Interrupt
Time
7126 Function Test the input breaker interruption time
response time. Input breaker will open
during test.
Drive Has Input
Breaker
7127 Yes Indicates that drive has input breaker that
is under NXGpro software control. Op‐
tions are:
Yes
No
Table 6-90 Single Phasing Menu (7010) Parameters
Parameter ID Unit Default Min Max Description
SPD prop gain 7020 0.0 0.0 10.0 Single phase detector PI regulator propor‐
tional gain term.
SPD integral
gain
7030 0.001 0.0 1.0 Single phase detector PI regulator integral
gain term.
SPD threshold 7040 % 50.0 0.0 100.0 Regulator output level below which an
alarm is generated.
Table 6-91 Drive Security Reset and Secure System Keys (for USB 󹪞ash disk)
Parameter ID Description
Reset Credentials 7748 Reset DCR password for use with ToolSuite
Create Factory Key 7749 Create nxgrecover.factory secure key 󹪝le on USB
Create Restore Key 7750 Create nxgrecover secure key 󹪝le on USB
Create Emergency Key 7751 Create nxgemergency secure key 󹪝le on USB
Create Update Key 7752 Create nxgupdate secure key 󹪝le on USB
Parameter 7748, Reset Credentials, resets the ToolSuite nxgproplus user login password to
"nxgproplus".
Spare controllers are usually shipped with the following password scheme, unless otherwise
speci󹪝ed:
DCR serial # example: Y20010001aa!
Parameter Assignment/Addressing
6.16 Options for Drive Protect Menu (7) - part 2
NXGPro+ Control Manual
Operating Manual, A5E50491925A 159

Table of Contents

Other manuals for Siemens SINAMICS PERFECT HARMONY GH180

Related product manuals