The calculation of drive losses depends on input and output power calculations. Due to this
dependency it is important to ensure that the following values are correctly set:
Drive input and output rated values, voltage and current:
Rated input voltage (2010)
Rated input current (2020)
Rated output voltage (2030)
Rated output current (2040)
Drive input scalers
Input current scaler (3030)
Input voltage scaler (3040)
Input CT turns ratio
CT secondary turns (3035)
Output scalers
Output current scaler (3440)
Output voltage scaler (3450)
Low Freq Wo (3070)
Implementation
The following 󹪝gure shows the implementation of the drive loss fault circuit.
,QSXW3RZHU
2XWSXW3RZHU,QSXW7KUHVKROG
,QWHUQDO7KUHVKROG
)DXOW
'ULYH/RVVHV
,QYHUVH7LPH
LQ,GOH6WDWH
LQ5XQ6WDWH
ūū
Figure 7-19 Implementation of the Drive Loss Fault Circuit
Operating the Control
7.9 Input Side Monitoring and Protection
NXGPro+ Control Manual
Operating Manual, A5E50491925A 209