1. Once the M1 acknowledge is received, M4 is commanded to open.
2. With the acknowledge of M4 open, the following checks occur:
input voltage must be above 80%
pre-charge contactors (M2, M3, and M4) must all be open
SOP 󹪞ag MainInputVoltageDisable_O must be false.
3. Pre-charge is complete, the PrechargeComplete_I 󹪞ag is set true and the drive is connected
to the MV source and ready to run. The pre-charge state machine is exited and the exit state
is recorded in the event log along with all other recorded pre-charge events in the sequence.
Note
The drive run is inhibited until pre-charge completes successfully.
On a successful pre-charge, the state machine remains in PC_COMPLETE until reset. It will cycle
back to pre-charge faulted (without fault) to begin again.
Setting Parameters for Type 6 Pre-charge
Use the following parameter settings to operate type 6 pre-charge. Refer to Cell Menu (2520) in
Section Options for Drive Menu (2) of Chapter Parameter Assignment / Addressing for
parameters associated with this function.
For normal operation:
Pre-charge Enable (2635) to "Type 6 Closed".
Use type 6 pre-charge for any cell type, but cell voltages (2550) "750V AP" and "750V AP
4Q" must use either type 5 or type 6 pre-charge. These are the two settings that are
de󹪝ned for the water-cooled 6SR325 drive.
For maintenance or service operation:
Precharge Service Mode (2637). This parameter completes pre-charge with M4 closed.
M1 never closes. Use for troubleshooting purposes only.
Pre-charge Service Start (2638). This parameter starts the service mode of pre-charge
from the menu instead of through an SOP 󹪞ag.
NOTICE
Changing drive parameter settings
Do not change drive parameter settings.
Only Siemens trained personnel are authorized to change drive parameter settings.
See also
Pre-charge using Dedicated I/O (Page 269)