EasyManua.ls Logo

Siemens SINAMICS PERFECT HARMONY GH180 - Page 293

Siemens SINAMICS PERFECT HARMONY GH180
538 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7UDQVIRUPHUZLWK
9,VRODWHG
6HFRQGDULHV
,QGXFWLRQ
0RWRU
&HOO
$
&HOO
%
&HOO
&
,QSXW3RZHU
SKDVH$&
,QSXW3RZHU
SKDVH$&
&HOO
$
&HOO
%
&HOO
&
&HOO
$
&HOO
%
&HOO
&
&HOO
$
&HOO
%
&HOO
&
3UHFKDUJH9ROWDJH
2KPSHUSKDVH
0)'SHUSKDVH
WR9
SKDVH6RXUFH
3UHFKDUJH&XUUHQW
3UHFKDUJH:LQGLQJ
0
0
0
9
Figure 8-16 Type 1 Pre-charge Component Connections
Sequence of Operation
1. To start pre-charge, DriveReadyToPrecharge_I must be
true. PrechargeStartEnable_O is set true to start the sequence.
2. M2 is closed to begin resonance by connecting a capacitor in series with the
secondary, PrechargeM2Close_I is set equal to true.
3. When the input primary voltage reaches the max phase voltage set by the parameter
"Precharge voltage level" (2634), a damping resistor is connected through
M3. PrechargeM3Close_I is set equal to true.
4. The M3 acknowledge comes back, PrechargeM3CloseAck_O is set equal to true. M2
contactor is commanded to open, PrechargeM2Close_I is set equal to false.
5. The M2 acknowledge comes back, PrechargeM2CloseAck_O is set equal to true. M1
contactor is commanded to close, PrechargeM1Close_I is set equal to true.
Advanced Operating Functions
8.18 Pre-charge using SOP
NXGPro+ Control Manual
Operating Manual, A5E50491925A 291

Table of Contents

Other manuals for Siemens SINAMICS PERFECT HARMONY GH180

Related product manuals