Cell diagnostics are not performed until precharge is complete (M1 closes and begins once the
Input voltage exceeds 60% of rated).
If all precharge conditions are met, the DriveReadyToPrecharge_I 󹪞ag is true". Otherwise, the
DriveReadyToPrecharge_I 󹪞ag is set false. Therefore this 󹪞ag should be used as part of the
conditions to start pre-charge. Precharge cannot be initialized or started if this 󹪞ag is not true.
Once precharge commences, the 󹪞ag goes false and remains false until all conditions are again
met.
When all conditions are met, the pre-charge state machine advances from the initial state of
"PRECHARGE_FAULTED" through "INIT_PRECHARGE2", into the "PRECHARGE_READY" state. The
loss of the DriveReadyToPrecharge_I 󹪞ag causes the state machine to cycle back to
"INIT_PRECHARGE2" until the drive is ready.
Fault and status messages will closely follow existing messages for type 5 and 6 except where
new or di󹪜erent.
The precharge circuit breaker is commanded to open under the following conditions during
precharge, resulting in precharge fault:
Over-voltage (>115 %) occurs during pre-charge
Under-Voltage Trip (PCVMRStatus_O)
Input Protection Fault
LFR Trip
E-Stop (PB-4)
M2 Contactor Open Status Failure
Trip_CB2 is asserted (TripPrechargeCB2_O) through the SOP
The CB trip can only be controlled via the setting of an SOP 󹪞ag (ClosePrechargeCB_I) to trip the
CB. To simplify, this 󹪞ag will be used so that the desired action can be set to a single output point.
In addition to being triggered by an internal event, the setting of the SOP Input 󹪞ag
TripPrechargeCB2_O, will also set the Output SOP 󹪞ag ClosePrechargeCB_I.
Conditions to set the drive ready for precharge
The following are the conditions which set the DriveReadyToPrecharge_I 󹪞ag:
Type 4 precharge selected
Drive not running
MV is low (not OK)
Output to close M1 is open, DO-14 – CIMV
Output to M1 Permissive is open, (FPGA_M1_PERMIT) – SIB 51, 53, 55 TIMV
M1 is open, M1 Close Ack – PrechargeM1CloseAck_I – SOP 󹪞ag
M2 is open, M2 Close Ack – PrechargeM2CloseAck_I – SOP 󹪞ag
Pre-charge circuit breaker is closed – CB2Status_O is true – SOP 󹪞ag
Pre-charge voltage monitor permissive is good – PCVMRStatus_O is true – SOP 󹪞ag
Trip precharge circuit breaker 󹪞ag false - TripPrechargeCB2_O - command to trip is false - from
SOP
No medium low fault
Advanced Operating Functions
8.19 Pre-charge using Dedicated I/O
NXGPro+ Control Manual
Operating Manual, A5E50491925A 299