Example for changing motor frequency parameters:
1. Press [SHIFT] [⇒] to get to the parameter ID display.
Enter parameter ID for motor frequency (1020).
E n t e r P a r a m I D
S p e e d P a r a m e t e r
1 0 2 0
Figure 9-54 Status display after pressing [SHIFT] [⇒] and entering ID 1020
2. Press the [ENTER] key once to show the motor frequency display and then press [ENTER]
again to edit its value.
H z
0 1 0 . 0 ( e d i t )
M o t o r f r e q u e n c y
Figure 9-55 Status display after pressing [ENTER] twice
The range of the variable is 15 to 330.
If, for example, you attempt to enter 010 for the motor frequency an error message will be
displayed for approximately four seconds.
Then the value shown before the attempted edit is displayed again.
O U T O F R A N G E
M o t o r f r e q u e n c y
Figure 9-56 Status display upon entering a value beyond the range of the system
Summary of Operation Mode Displays
The following tables list the possible operational mode displays of line 1 and 2 of the display in
order of precedence.
Table 9-9 Line 1 of mode eld
Order Code Meaning Description
1 FRST Fault reset Displayed after the [FAULT RESET] button is pressed.
Note: This may not be visible because of the speed of response to a fault
reset.
2 TLIM Menu setting rollback Drive is being limited by a menu setting.
3 SPHS Single phasing rollback A single phasing condition of the input line is limiting drive torque.
4 UVLT Undervoltage rollback A undervoltage condition of the input line is limiting the drive torque.