USB 󹪞ash disk requirement
1. The 󹪞ash disk must be FAT32.
Insert a USB 󹪞ash disk.
Open File Explorer.
Right-click on the USB drive and select Propeties.
Flle system: FAT32
2. The FAT32 partition must be the 󹪝rst primary partition.
3. The 󹪞ash disk must have a drive label.
Insert USB 󹪞ash disk.
Open File Explorer
Right-click on the USB drive and select Propeties.
The entry 󹪝eld next to the picture should have a label. Example: USB8GB (length should
be 1-8 characters)
4. The 󹪞ash disk should be USB2.0.
NOTICE
Known issues with USB 󹪞ash disk
Only one manufacturer/type of 󹪞ash disk was tested; Sandisk Cruzer Glide 16 GB USB2.0.
Verbatim Cle USB 󹪞ash disks are not recognized
For other USB 󹪞ash disks brands and types, the two known failure of USB 󹪞ash disks modes
are:
Cannot mount and/or write to 󹪞ash disk.
The secure system keys are ignored on startup, and the emergency/update/recover keys
cannot be used.
Keypad error messages
The following message de󹪝nitions will be displayed on the keypad as “Error. See eventlog. #9xx”,
where xx is one of the following errors.
Error 900 – USB partition error (e.g. not 1st partition or not FAT32).
Error 901 USB unmount error (can generally be ignored but might indicate 󹪞ash disk errors).
Error 902 – USB unmount retry error (can generally be ignored but might indicate 󹪞ash disk
errors).
Error 903 USB mount error (e.g. 󹪞ash disk not recognized, not FAT32, 󹪝le/disk corruption).
USB usage while drive running
The NXGPro+ has two interlocks that a󹪜ect USB functionality. One is so that all USB port
functionality will not start from keypad while drive is either: Not CR3 Inhibited, Not Idle, or Not
Faulted. That is, the drive must be CR3 Inhibited, Idle, or Faulted to use USB functionality. The
other is that the drive cannot be started while any USB function is active processing the keypad
request. The latter requires an SOP 󹪞ag ReadyToRun_I as part of the TempFlag01_O main 󹪞ag.