Fault display Type Enable Potential causes and corrective actions
In torque limit A SOP Cause
This alarm is issued when the drive is in speed rollback, due to a torque
limit condition, for more than 1 minute.
Action
1. Check load conditions.
2. Check proper settings for drive and motor ratings.
In torq limit rollback F/A SOP Cause
This fault or alarm, depending on the SOP, is issued when the drive is in
speed rollback, due to a torque limit condition, for more than 30 minutes.
Action
1. Check load conditions
2. Check proper settings for drive and motor ratings.
Minimum speed trip F/A SOP Cause
Motor speed is below the zero speed setting (2200). This is either due to
a motor stall condition, if speed demand is higher than the zero speed
setting, or a low speed demand condition, where speed demand is lower
than the zero speed setting.
Action
Increase motor torque limit (1190, 1210 or 1230) if it is a stall condition
or adjust the zero speed setting to avoid the desired low speed operating
region.
Loss of 󹪝eld current F/A SOP Cause
This occurs only with synchronous motor control due to 󹪝eld exciter failure
or loss of power to the exciter.
Action
Check if the power supply to the exciter is energized. To determine if the
󹪝eld exciter is operating correctly:
reduce Flux demand (3150) to 0.40, increase Accel time 1 (2270) to a
larger value and run the motor with 5% speed demand.
If the drive magnetizing current reference (I
ds,ref
) does not go to zero,
then the 󹪝eld exciter is not working or is not adjusted properly.
Troubleshooting Faults and Alarms
11.5 Drive Faults and Alarms Motor/Output Related
NXGPro+ Control Manual
452 Operating Manual, A5E50491925A