Fault display Type Enable Potential causes and corrective actions
Int I/O Cong Fault F Fixed Cause
Three dierent errors can generate this fault:
1. Bad module type. A received module type is not supported by the
system. There are currently two types supported:
– module type "1": 20 digital inputs and 16 digital outputs
– module type "2": 20 digital inputs, 16 digital outputs, 3 analog
inputs and 2 analog outputs
2. No modules found. No modules were found by the system and one or
more of the expected types set by the menu parameters are non-zero.
3. Wrong module type. A module type does not match the expected type
set by the menu parameters.
Action
1. Ensure correct number of modules and types are set in the menu.
2. Check ber optic cables to modules.
3. Replace aected user I/O module.
4. Contact Siemens customer service.
Int I/O Module Address F Fixed Cause
This fault is generated when the system nds that a module’s reported
previous address does not match its current address.
Action
1. Check that the ber optic chain is correct and the correct module is in
the correct position within it.
2. This condition can be corrected through the use of the "Set User I/O
Module Addresses Function".
3. If the "Set User I/O Module Addresses Function" doesn’t x this, contact
Siemens customer service.
Int I/O Watchdog Fault F Fixed Cause
The rmware reports that the software has not transmitted the watchdog
bit in the User I/O Control register within the timeout period of 5 millisec‐
onds.
Action
1. Toggle DCR power.
2. Replace DCR rack.
3. Contact Siemens customer service.