Fault Display Type Enable Potential Causes and Corrective Actions
Loss All HEX Fans F/A SOP Cause
Drive initiated alarm/fault when the LossAllHexFan_O
SOP ag is set true and the LossAllHexFanEn_O ag is
true to enable it. The default is an alarm but it can be changed
to a fault by setting the LossAllHexFanWn_O ag to False
(true is an alarm). This is used in the Standard SOP for water-
cooled drives as an alarm.
Action
1. Check physical input connected to SOP ag.
2. Check sensor.
3. Check for faulty fan..
4. Check for obstruction.
All HEX Fans On A SOP Cause
Drive initiated alarm when the AllHexFansOn_O SOP ag
is set true and the AllHexFansOnEn_O ag is true to enable
it. The default is an alarm and it cannot be changed. This is
used in the Standard SOP for water-cooled drives as an alarm.
Action
1. Check physical input connected to SOP ag.
2. Check sensor.
3. Check for faulty fan.
4. Check for obstruction.
Troubleshooting Faults and Alarms
11.13 Dedicated I/O for Input Protection
NXGPro+ Control Manual
492 Operating Manual, A5E50491925A