Note
Tripped Pre-charge Circuit Breaker Occurrences
The pre-charge circuit breaker shall be tripped if any of the following occurs:
• Over-voltage (>115%) occurs during pre-charge
• Under-Voltage Trip (PCVMRStatus_O)
• Input Protection Fault
• LFR Trip
• PB4/E-Stop
• M2 Contactor Open Status Failure
• Trip_CB2 (TripPrechargeCB2_O) is asserted
The SOP input control ags below are available for particular cell types using the pre-charge
function by selecting Type 4 pre-charge. No dedicated inputs are used.
Table 5-3 Type 4 SOP Input Control Flags
Flag Function Description
StartCellPrecharge_O PrechargeRequest Request to start pre-charge
PrechargeM2CloseAck_O M2CloseACK Feedback of M2 contact
PrechargeM1CloseAck_O M1CloseACK Feedback of M1 contact
TripPrechargeCB2_O (SOP) TripPrechargeCB2 Request trip of pre-charge CB
PCVMRStatus_O PCVMRStatus Precharge voltage (CB UV trip) status - '1' = voltage okay
CB2Status_O CB2Status Precharge CB status - '1' = CB is closed
There are 16 digital outputs on the rst user I/O board:
• DO-0 to DO-15
There is one digital output on the system interface board:
• SIB M1 DOUT
Table 5-4 Type 4 Dedicated and SOP Outputs
Dedicated Output* Terminal SOP Feedback Function Description
DO-14 J4-7, 8, 9 CIMVType4 CIMV Command to close M1
PrechargeM2Close_I Assigned out‐
put
SOP determined M2Close Command to close M2
OpenPrechargeCB_I Assigned out‐
put
SOP determined BreakerTrip Command to open (trip) pre-charge supply
breaker
M1 DOUT SIB 51, 53, 55 M1Permit‐
Closed_I
M1Close
Permissive
(TIMV)
If this signal is de-energized, the drive’s medi‐
um voltage will trip immediately.
If the signal is not energized, it will be an in‐
hibit.
* Dedicated Output: Refer to specic drive wiring diagram for dedicated output designations
Hardware User Interface Description
5.3 User Accessible Interfaces
NXGPro+ Control Manual
78 Operating Manual, A5E50491925A