EasyManua.ls Logo

Siemens SINUMERIK 802D sl - Page 128

Siemens SINUMERIK 802D sl
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.1 Creating a drive project OFFLINE
Creating a Drive Project
10-126
SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition
6FC5 397-0CP10-1BA0
Fig. 10-5 Setting up the PG/PC interface: Properties
7. The system has determined all possible interfaces on your PC (e.g. Serial Cable (PPI)).
Select an interface via the Interface parameterization used list box; thereafter, click on
the Properties button and adapt the baud rate to the settings in the 802D sl
(default: 115.2 kbit/s).
Alternative: The connection can be established via the TCP/IP protocol. To this end,
connect the PC/PG to the CU directly using a X Crosslink patch cable or a standard
patch cable via the corporate LAN.
The following additional steps of operation are required here:
Use the mouse to select the drive unit in the Project Navigator.
Open the selection menu by clicking on the right mouse button.
Use “Target device online access” to load data into the interactive dialog box which is
now displayed (see Fig. 10-6).
Slot 25 and the IP address do not comply with the default configuration.
In corporate networks, the IP address assigned by the administrator must be entered;
with direct connection, the SINAMICS is assigned the fixed IP address 169.254.11.22
in 802D.
When establishing a connection via Crosslink, the IP address of the PC/PG
(169.254.11.23) must be entered in the user-defined, alternative configuration
(see Fig. 10-8).
For corporate networks with DHCP server, the password for protection level 1 must be
entered via HMI. Use System > Service display > Service control system >
Service network to change the DHCP entry to yes.

Table of Contents

Other manuals for Siemens SINUMERIK 802D sl

Related product manuals