Operating   
6.2 Operating modes 
  SIPART PS2 with and without HART 
108  Operating Instructions, 10/2013, A5E00074631-11 
In this mode, you move the actuator with   or  . The setting selected here is retained 
irrespective of the setpoint current and leakages, if any. 
 
Note 
Accelerating the actuator movement 
Proceed as follows if you wish to accelerate the actuator movement:
 
  Keep one of the two direction buttons pressed. 
  Press the remaining direction button simultaneously. 
 
Note 
Failure of power supply 
When t
he power supply is reestablished after a failure, the positioner switches to the 
 
Automatic is the standard mode. In this mode, the positioner compares the setpoint position 
with the actual position. The positioner moves the actuator until the control deviation reaches 
the configurable deadband. A fault message is displayed if the deadband cannot be reached. 
 
out of service; reaction: last position is retained. 
initialization manual mode 
RCS  RCAS  remote cascade 
Proceed as follows to call the "Diagnostics" mode from the "Automatic" or "Manual" modes: 
Press the three buttons of the positioner at the same time for at least 2 seconds. 
Current operating data can be called and displayed in this mode, e.g.: