Commissioning
7.4 Commissioning linear actuators
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
131
Aborting the manual initialization process
1. Press the button. The display shows the "5.INITM" parameter. The positioner is in the
"Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
button for at least 5 seconds. The
software status is displayed. After releasing the
button, the positioner is in "P manual
mode". The positioner is not initialized.