EasyManua.ls Logo

Solcon HRVS-DN series - Discrete Commands (Coils, 0 X References)

Default Icon
181 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
143 • HRVS-DN Communication (ModBus Protocol)
_______________________________________________________________________________________________
byte 10: CRC_Low ($XX)
byte 11: CRC_High ($XX)
The HRVS-DN normal response:
byte 1: Serial Link No. ($0B)
byte 2: Function ($10)
byte 3: Starting Address High ($02)
byte 4: Starting Address Low ($F0)
byte 5: No. of Registers High ($00)
byte 6: No. of Registers Low ($01)
byte 7: CRC_Low ($XX)
byte 8: CRC_High ($XX)
16.10 Discrete Commands (Coils, 0x References)
The HRVS-DN incorporates 16 "Coils", (bit parameters), from which only 3 are operative. The other 13 are
reserved and were incorporated to enable the user to use word (16 bits) type parameters. Coil # is 1"1
based". The actual address is 1 lower than coil #. For example coil #1 is addressed as 0 (00000). Use
functions 5 or 15 to send control commands to the starter.
The coils have the following 0x references:
Coil # Coil Address Use in HRVS-DN Comment
1 0 Reserved.
2 1 Reserved.
3 2 Reserved.
4 3 Start/Stop Relay Write "1" (ON) to Start / Run.
Write "0" (OFF) to Stop.
5 4 Dual Adjust Write "1" (ON) to turn On.
Write "0" (OFF) to turn Off.
6 5 Reserved.
7 6 Reserved.
8 7 Reset Write "1" (ON) momentarily to Reset.
Rejected, if given together with Start command.
9..16 8..15 Reserved
Example 6 - Read Coils:
To read coils 1..8 status of HRVS-DN # 10, the host computer sends the following Query frame:
byte 1: Serial Link No. ($0A)
byte 2: Function ($01)
byte 3: Starting Address High ($00)
byte 4: Starting Address Low ($00)
byte 5: No. of Coils High ($00)
byte 6: No. of Coils Low ($08)
byte 7: CRC_Low ($XX)
byte 8: CRC_High ($XX)
The HRVS-DN response, when coils 7..0 are OFF OFF OFF ON OFF ON OFF OFF:
byte 1: Serial Link No. ($0A)
byte 2: Function ($01)
byte 3: Byte Count ($01)
byte 4: Data (coils 7..0) ($14)
byte 5: CRC_Low ($XX)
byte 6: CRC_High ($XX)
Example 7 - Force Single Coil:
To start the motor controlled by HRVS-DN # 1, the host computer writes "1" to the "START/STOP COIL" (coil
4 addressed as 3) .

Table of Contents

Related product manuals