52 • Control Keypad
_____________________________________________________________________________________________
7.8 Overview of All Mode Pages and Factory Defaults
Appears only in
MAXIMIZED MODE
(1)
DISPLAY MODE PAGE MAIN & PROTECT
- **** -
START PARAMETERS
- **** -
STOP PARAMETERS
- **** -
DUAL ADJUSTMENT
PARAMETERS
Display and default
values
Display and default
values
Display and default
values
Display and default
values
Display and default
values
I1 I2 I3
0 0 0 %
RATED LINE VOLT.
6600 VOLT
SOFT START CURVE
1 (STANDARD)
SOFT STOP CURVE
1(STANDARD)
DA: INIT. VOLT.
30%
I1 I2 I3
0 0 0 A
STARTER FLC
150 AMP.
START TACHO. GAIN
(2)
0(MIN. GAIN)
STOP TACHO. GAIN
0(MIN. GAIN)
DA: INIT. CURRENT
(2)
100%
VOLTAGE FREQ.
3,300V 49.9Hz
MOTOR FLA
150 AMP.
PULSE LEVEL
70% OF FLA
DEC. TIME
0 SEC.
DA: CUR. LIMIT
400% OF FLA
POWER
1,500 KW
RATED MOTOR PWR
1000 KW
PULSE TIME
0.0 SEC.
FINAL TORQUE
0 (MIN.)
DA: ACC. TIME
10 SEC.
REACTIVE POWER
500 KVAR
SERVICE FACTOR
100 %
INITIAL VOLTAGE
30 %
COAST DOWN DELAY
OFF
DA: DEC. TIME
0 SEC.
POWER FACTOR
0.85
UNDERCURR. TRIP
0% OF FLA
INITIAL CURRENT
(2)
100 %
STORE ENABLE
STOP PARAMETERS
DA: MOTOR FLA
150 AMP.
THERMAL CAPACITY
0 %
UNDERCURR. DELAY
10 SEC.
CURRENT LIMIT
400% OF FLA
STORE ENABLE
D. ADJ. PARAMETERS
MOTOR INSULATION
(2)
52.8Mohm
O/C – SHEAR PIN
850% OF FLA
ACC. TIME
10 SEC.
OPTION CARD
NOT INSTALLED
O/C DELAY
0.5 SEC.
MAX. START TIME
30 SEC.
OVERLOAD CLASS
IEC CLASS 10
NUMBER OF STARTS
1
OVERLOAD
PROTECT
ENABLE WHILE RUN
STARTS PERIOD
20 MIN.
UNBALANCE TRIP
20% OF FLA
START INHIBIT
15 MIN.
UNBALANCE DELAY
5 SEC.
RUN CONTACT DLY
5 sec.
GND FAULT TRIP
20% OF FLA
TURN BYPS ON AT
(2)
120% OF FLA
GND FAULT DELAY
5 SEC.
MIN TIME TO BYPS
(2)
3 SEC.
UNDERVOLT. TRIP
70% OF Vn
STORE ENABLE
START PARAMETERS
UNDERVOLT. DELAY
5 SEC.
OVERVOLT. TRIP
120% OF Vn
OVEERVOLT. DELAY
2 SEC.
STORE ENABLE
MAIN & PROTECT.
(1)
- Refer to section 6.4.1 on page 40 for changing mode from MINIMIZED MODE to MAXIMIZED MODE.
(2)
- Parameter viewed only when used.