49 • Control Keypad
_______________________________________________________________________________________________
The Test LED will turn off and the LCD will display:
SELF TEST PASSED
And after a few seconds the LCD will display:
I1 I2 I3
0 0 0 %
7.6.2 View Software Version
Press the Mode and ▼ keys simultaneously.
The Test LED will light and the LCD will display:
TEST/MAINTENANCE
***OPTIONS***
Press the Select key twice.
The LCD will display:
BTL-R-16/09/2008
MVSTMB.GN-121008
Press the Mode and ▼ keys simultaneously to exit the TEST/MAINTENANCE mode.
The Test LED will turn off and he LCD will display:
I1 I2 I3
0 0 0 %
7.6.3 Obtain Default Parameters
Press the Mode and ▼ keys simultaneously.
The Test LED will light and the LCD will display:
TEST/MAINTENANCE
***OPTIONS***
Press the Select key three times.
The LCD will display:
STORE ENABLE
DEFAULT PARAMET.
Press the Store + Mode keys simultaneously.
The Test LED will turn off and the LCD will display:
DATA SAVED OK
And after a few seconds the LCD will display:
I1 I2 I3
0 0 0 %
CAUTION!
Obtaining DEFAULT PARAMETERS erases all previously modified settings
and requires the operator to reprogram all parameters that differ from the
factory default.
Note
: It is especially important to reprogram the RATED LINE VOLTAGE and
STARTER FLC (as shown on the label of the HRVS-DN) and all other
parameters in MAIN & PROTECT mod page. Refer to section
7.8.2 page 55.
7.6.4 Reset Statistical Data
Press the Mode and ▼ keys simultaneously.
The Test LED will light and the LCD will display:
TEST/MAINTENANCE
***OPTIONS***
Press the Select key four times.
The LCD will display:
RESET STATISTICS
Press the Reset + Store keys simultaneously.
The Test LED will turn off and the LCD will display: