167 • HRVS-DN Communication (DeviceNet™)
_______________________________________________________________________________________________
18.5 Assembly Object (04HEX – 4 Instances)
18.5.1 Class Attributes (Instance 0)
Attribute
ID
Name DeviceNet
Data Type
Data
Value
Access
Rule
1 Revision UINT 2 Get
2 Max Instance UINT 112 Get
100 Input Index
60 = Instance 60
61 = Instance 61
100 = Instance 100
USINT 2 Get / Set
5
101 Input Size (in bytes) UINT 1 Get
102 Output Index
112 = Instance 112
USINT 0 Get / Set
6
103 Output Size (in bytes) UINT 1 Get
18.5.2 Output (O2T) Instance Attributes – Register 40752
Attribute
ID
Name DeviceNet
Data Type
Data
Value
Access Rule
3 Output Data USINT[] 0 Get/Set
18.5.2.1 Output Instance 112 (0x70 – Attribute 3) – Control Output
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
0 1 0 1 1 0 1 0
1 Reset Reserved Reserved
Dual
Adjust
Start/Stop
Relay
Reserved Reserved Reserved
18.5.3 Input (T20) Instance Attributes – Register 40257
Attribute
ID
Name DeviceNet
Data Type
Data
Value
Access
Rule
3 Input Data USINT[] 0 Get
18.5.3.1 Input Instance 60 (0x3C) – Basic Softstart Input
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
At
Reference
Reserve
d
Reserve
d
Reserve
d
Reserve
d
Running
1
Reserve
d
Faulted /
Trip
18.5.3.2 Input Instance 61 (0x3D) – Extended Softstart Input
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
At
Reference
Reserved
Control
From
Net
Ready Running2 Running1 Warning
Faulted /
Trip
5 Stored to NVRAM