161 • HRVS-DN Communication (Profibus protocol)
_______________________________________________________________________________________________
17.8 Number of Setting Registers for Data Request
17.8.1 Main & protect. parameters
Parameter # Range Default
Rated Line Voltage 0 2300..15000 6600 (Volt.)
Starter FLC 1 20..1800 150 (Amp.)
Motor FLA 2 20..1800 150 (Amp.)
Rated Motor Power 3 50..40000 1000 (KW)
Service Factor 4 100..130 (% of FLA) 100 (%)
Undercurrent Trip 5 0..90 0 (% of FLA)
Undercurrent Delay 6 1..40 10 (Seconds)
Overcurrent Shear Pin 7 100..850 850 (% of FLA)
Overcurrent Delay 8 0..50 5 (0.5 Sec.)
Overload Class 9
IEC 5,10,15,20,25,30
NEMA 5,10,15,20,25,30 FLA)
IEC Class 10
Overload Protect 10
0=Disable
1=Enable While Run
2=Enable
1=Enable While Run
Unbalance Trip 11
10..100, 101 = Off
20 (%)
Unbalance Delay 12
1..60
5 (Seconds)
Ground Fault Trip 13
10..100, 101 = Off
20 (% of FLA)
Ground Fault Delay 14
1..60
5 (Seconds)
Undervoltage Trip 15
50..90
70 (%)
Undervoltage Delay 16
1..100
5 (Seconds)
Overvoltage Trip 17
110..125
120 (%)
Overvoltage Delay 18 1..10 2 (Seconds)
Reserved 20..24
17.9 Start Parameters
Parameter # Range Default
Soft_Start_Curve 24
0..11 (6..11 are for Tacho
only)
1 (Standard).
Pulse Level 25 70 (%of FLA) – 700 (%of FLA) 70% of FLA
Pulse Time 26 0..10 (Tenth Seconds) 0 (No Pulse)
Initial Voltage /
Initial Current
27
10..80 /
100..400 % (of FLA)
30 (% of full voltage) /
100 (% of FLA)
Current Limit 28 100..700 400 (% of FLA)
Acceleration Time 29 1..90 10 (Seconds)
Max. Start Time 30 1..250 30 (Seconds)
Number Of Starts 31 1..10 & (11 = off) 1
Starts_Period 32 1..60 20 (Minutes)
Start Inhibit
33 1..60 minutes 15 (Minutes)
Run Contact Delay /
Turn Bypass On at
34
0..120 seconds /
121..250 % of Motor FLA
5 (Seconds) /
Only with relay card for
optional sync motor start
Min Time To Bypass
35 3..60
3 Sec
Only with relay card for
optional sync motor start
Reserved
36..39