174 • HRVS-DN Communication (DeviceNet™)
_____________________________________________________________________________________________
Attribute
ID
Name Range Default
Value
Access
Rule
Modbus
Address
12 Unbalance Trip 10-100,
101 = Off
20 (%) Get/Set 40012
13 Unbalance Delay 1-60 5
(Second
)
Get/Set 40013
14 Ground Fault Trip 10-100,
101 = Off
20 (% of
FLA)
Get/Set 40014
15 Ground Fault Delay 1-60 5
(Second
)
Get/Set 40015
16 Under voltage Trip 50-90 70 (%) Get/Set 40016
17 Under voltage Delay 1-100 5
(Second
)
Get/Set 40017
18 Overvoltage Trip 110-125 120 (%) Get/Set 40018
19 Overvoltage Delay 1-10 2
(Second
)
Get/Set 40019
18.11.3 Common Services
Service
Code
Implemented for Service Name
Class Level Instance Level
0E
HEX
Yes Yes Get Attribute Single
10
HEX
No Yes Set Attribute Single
18.12 Start Settings Object (72HEX – 1 Instance)
18.12.1 Class Attributes (Instance 0)
Attribute
ID
Name DeviceNet
Data Type
Data Value
Access
Rule
1 Revision UINT 1 Get
18.12.2 Instance Attributes (Instance 1)
Attribute
ID
Name Range Default
Value
Access
Rule
Modbus
Address
1 Soft Start Curve 0-11 (6-11 are for
Tacho only)
1
(Standard
)
Get/Set 40025
2 Pulse Level 70 (%of FLA) –
700 (%of FLA)
70% of
FLA
Get/Set 40026
3 Pulse Time 0-10 (Tenth
Seconds)
0 (No
Pulse)
Get/Set 40027
4 Initial Voltage/
Initial Current
10-80 /
100-400 % of
FLA
100 % of
FLA
Get/Set 40028
5 Current Limit 100-700 400 (% of
FLA)
Get/Set 40029
6 Acceleration
Time
1-90 10
(Seconds)
Get/Set 40030
7 Max. Start Time 1-250 30
(Seconds)
Get/Set 40031
8 Number Of
Starts
1-10 & (11 = off) 1 Get/Set 40032
9 Starts Period 1-60 20
(Minutes)
Get/Set 40033
10 Start Inhibit 1-60 minutes 15
(Minutes)
Get/Set 40034
11 Run Contact
Delay
0-120 seconds 5
(Seconds)
Get/Set 40035

Table of Contents

Related product manuals