163 • HRVS-DN Communication (Profibus protocol)
_______________________________________________________________________________________________
Parameter # Range Default
Ser. Link Control 85 0 (Disable), 1 (Enable) 0 (Disable control)
Modbus Time Out 86 1..247 & (248= Off) 248 (Off)
Front Com Address 87 1..600 & (601= Off) 601 (Off) (Off) (Tenth Sec)
Reserved 88
Modbus_#_Array 89..108 # of parameter
Defaults # are:
1 - Logic Status
5 – I1
6 – I2
7 – I3
4 – Voltage
2 – Ctrl-In
3 – Ctrl_Out (relays)
15 – Power
17 – Power Factor
19 – Frequency
10 – Phase Sequence
26 – Total Run Time
27 – Total Starts
31 – Total Trips
28 – Last Start Period
29 – Last Start Peak I
32 – Last Trip Number
33 – Pre Trip I
39 – Thermal Capacity
11 – Insulation Resistance
17.15 Time Parameters
Parameter # Range Default
Clk Hour 130 0 – 23 Set here, Read at actual # 41
Clk Minute 131 0 – 59 Set here, Read at actual # 42
Clk Month 132 1 – 12 Set here, Read at actual # 43
Clk Day 133 1 – 31 Set here, Read at actual # 44
Clk Year 134 0 – 99 Set here, Read at actual # 45