EasyManuals Logo

Solcon HRVS-DN series User Manual

Default Icon
181 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #146 background imageLoading...
Page #146 background image
146 • HRVS-DN Communication (ModBus Protocol)
_____________________________________________________________________________________________
16.11 Discrete Hardwired Inputs (1x References)
The HRVS-DN incorporates 16 Discrete Inputs, (bit parameters), from which only 6 are operative. The other
10 are reserved and were incorporated to enable use of word (16 bits) type parameters. Input # is "1 based".
The actual address is 1 lower than input #. For example input #1 is addressed as 0 (10000). The inputs have
the following 1x references:
Input # Address HRVS-DN use Comment
1 0 Stop Open Input (Input reads" 0") to Stop. (Terminal # 4)
Close Input (Input reads "1") to enable Start / Run.
2 1 Soft Stop Open Input (Input reads"0") to Soft Stop. (Terminal # 5)
Close Input (Input reads"1") to enable Start / Run.
3 2 Start Close Input (Input reads "1") to Start. (Terminal # 6)
4 3 Input # 1 Close Input (Input reads "1") to turn On. (Terminal # 7)
Open Input (Input reads "0") to turn Off.
Programmable to: 0- Test1
1- Slow Speed
2- Reset
5 4 Input # 2 Close Input (Input reads "1") to turn On. (Terminal # 8)
Open Input (Input reads "0") to turn Off.
Programmable to: 0- Dual Adjust
1- S. Spd Rvrs
2- Reset
6 5 Reserved
7 6 Ext. Fault 1 Close to Trip (Input reads" 1") (Terminal # 19)
8 7 Ext. Fault 2 Close to Trip (Input reads" 1") (Terminal # 20)
9..16 8..15 Reserved
Example 9:
To read all discrete inputs of HRVS-DN # 12, the host computer sends the following Query frame:
byte 1: Serial Link No. ($0C) (12)
byte 2: Function ($02)
byte 3: Starting Address High ($00)
byte 4: Starting Address Low ($00)
byte 5: No. of Points High ($00)
byte 6: No. of points Low ($08)
byte 7: CRC_Low ($XX)
byte 8: CRC_High ($XX)
The HRVS-DN response, when only Stop and Soft Stop terminals (Inputs 1&2) are connected:
byte 1: Serial Link No. ($0C) (12)
byte 2: Function ($02)
byte 3: Byte Count ($01)
byte 4: Data (Inputs 7..0) ($03)
byte 5: CRC_Low ($XX)
byte 6: CRC_High ($XX)
16.12 Diagnostics
Modbus Function 08 , as implemented in the HRVS-DN supports only Subfunction $0000. It provides for
"loopback" (Return Query Data) feature, for checking the Communication Serial Link between the master and
the HRVS-DN.
To request HRVS-DN # 1 to return Query data, the master should send following Query frame:
byte 1: Serial Link No. ($01)
byte 2: Function ($08)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Solcon HRVS-DN series and is the answer not in the manual?

Solcon HRVS-DN series Specifications

General IconGeneral
BrandSolcon
ModelHRVS-DN series
CategoryController
LanguageEnglish

Related product manuals