EasyManua.ls Logo

Solcon HRVS-DN series - Page 145

Default Icon
181 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
145 • HRVS-DN Communication (ModBus Protocol)
_______________________________________________________________________________________________
Example 8 - Force Multiple coils:
Motor that is controlled by HRVS-DN # 32 is stopped. Dual Adjust is set to off.
To start the motor using the Dual Adjust parameters , the host computer writes "1" to the Start and Dual Adjust
Coils no. 4 &5, addressed as 3 & 4. One of the many possible ways:
The "Query" frame sent by the host:
byte 1: Serial Link No. ($20)
byte 2: Function ($0F)
byte 3: Coil Address High ($00)
byte 4: Coils address Low ($00)
byte 5: No. of Coils High ($00)
byte 6: No. of coils Low ($08)
byte 7: Byte Count ($01)
byte 8: Force Data ($18) (coil # 4 & coil # 5)
byte 9: CRC_Low ($XX)
byte 10: CRC_High ($XX)
The normal (if no exception) response:
byte 1: Serial Link No. ($20)
byte 2: Function ($0F)
byte 3: Coil Address High ($00)
byte 4: Coils address Low ($00)
byte 5: No. of Coils High ($00)
byte 6: No. of coils Low ($08)
byte 7: CRC_Low ($XX)
byte 8: CRC_High ($XX)

Table of Contents

Related product manuals