7 Maintaining the product
192
Firmware System Update V1.X
valid for Saveris systems with base article no. 0572 0120,
0572 0121, 0572 0160, 0572 0161
Firmware System-Update V2.X
valid for Saveris systems with base article no. 0572 0220,
0572 0221, 0572 0260, 0572 0261
How long the firmware system update takes depends on the
number of Saveris components in the system. Automatic
distribution of the firmware to:
Converter and extender requires at least 3 minutes + 2
minutes per component for the standard communication
cycle.
Ethernet probe requires at least 3 minutes + 2 minutes per
component for the standard communication cycle.
Router requires at least 6.5 hours (all logged-in routers are
updated in parallel).
Radio probe in stationary use requires at least 16 hours (all
logged-in radio probes are updated in parallel).
The Saveris base must be connected to the computer via USB
or Ethernet cable.
All Saveris components must have at least firmware version
1.12 for the update. System components with firmware version
< V 1.12 can only be updated via service interface.
For an update to version 4.3, the components must be
equipped with the following firmware version as a minimum
requirement:
For V1.x systems: software 4.2 SP3, base and radio probe
V1.90, router, converter and extender V2.59, Ethernet probe
V1.47
For V2.x systems: software 4.2 SP3, base and radio probe
V2.59, router, converter and extender V2.59, Ethernet probe
V1.47
All outstanding alarms must be acknowledged by you before a
firmware system update.
ATTENTION: During the firmware update process, never
disconnect the power supply/network supply and the PC
connection.
During the update, measurements, data storage and data
communication are continued so there is no data loss.
Configuration changes during the firmware system update
should not be carried out to ensure that the process is not
slowed.
As there is heavy radio traffic during the update, alarms relating
to interrupted radio links may occur temporarily.

Table of Contents

Other manuals for TESTO Saveris

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TESTO Saveris and is the answer not in the manual?

TESTO Saveris Specifications

General IconGeneral
Humidity Range0 to 100 %RH
Measurement ParametersTemperature, Humidity
Data TransmissionWireless
Alarm FunctionYes
Resolution0.1 °C, 0.1 %RH
Radio Frequency868 MHz, 915 MHz
Data StorageInternal memory, Cloud
Power SupplyBattery