View Operation
OPERATION STATUS
Autosequencing and Standby Testing
1=ZONE 1
2=ZONE 2
3=ZONE 3
4=ZONE 4
5=RETURN TO MAIN MENU
SELECT A NUMBER:1
ZONE 1
AUTO SEQUENCING ON
DAY 01 OF 02 (08:55)
STANDBY TESTING ON
DAY 00 OF 03 (00:00)
STAGING ON
CURRENT VALUE 73.8 DEG
SET VALUE +0070.0 DEG
SENSITIVITY +005.0 DEG
1=VIEW A DIFFERENT ZONE
2=RETURN TO MAIN MENU
SELECT A NUMBER:
View Control Status
For details on this feature, see View Control Status on page47.
View Control Status
CONTROL STATUS
RELAYSTATUS
RELAY 1OFF
RELAY 2OFF
1=REFRESH CONTROL STATUS
2=RETURN TO MAIN MENU
SELECT A NUMBER:
Vertiv | Liebert® AC8 User Manual | 127