Alpha/Delta (Kinetic Operator) Installation and Maintenance Manual Revision 1 - MAY 2023
159
TROUBLESHOOTING
Table 12. SmartDC Controller - Troubleshoong
Ref.
No�
Display Descripon
Possible Causes Soluons
Condion Alert, Error or Fault
33 ALERT 25
HYNET LOW
BATTERY
Coin Cell Baery in
HyNet is Low.
Appears when a HyNet is
connected and reports that
the internal baery of the
HyNet is low.
Replace the baery in the
HyNet.
34 ALERT 28
BATTERY
DISCONNECTED
Baery disconnected
from board.
Dead or disconnected
baeries detected by SDC
board. Operator may sll
be funconal if on AC
power but will not have
baery backup. Was Error
9 in pre-h5.57 soware
versions.
Replace or reconnect baeries
to the controller.
35 FAULT 2
PHOTO EYE
The photo eye is missing
or not working.
This fault can only occur
if the special supervised
photo eye funcon is
enabled in the Installer
Menu. See “Installing
Photoelectric Sensors
for External Entrapment
Protecon Only” on page
145 for details.
Correct malfunconing photo
eye.
36 FAULT 3
VOLTAGE SAG
Not used in Kinec
operators.
N/A N/A
37 FAULT 4
GATE NO LOAD
The SmartDC Controller
has detected there is no
load on the operator.
The gate is non-
operaonal while this
fault is triggered.
Possible causes:
- Motor wires
disconnected.
- DC switch o.
1. Check DC motor wires;
check motor brushes.
2. Turn DC power switch on.
3. Press RESET to clear fault.
38 FAULT 5
LIMIT FAILED
Not used in Kinec
operators.
N/A N/A