TROUBLESHOOTING
Table 12. SmartDC Controller - Troubleshoong
Ref.
No�
Display Descripon
Possible Causes Soluons
Condion Alert, Error or Fault
39 FAULT 14
STUCK GATE
The SmartDC Controller
has tried 3 mes to
overcome a stuck
gate. The gate is non-
operaonal while this
fault is triggered.
Caused by broken gate
hardware or ice/snow
buildup.
1. Check and correct gate
hardware as required.
2. Press RESET to clear fault.
40 ERROR 1
DIRECTION
ERROR
The SmartDC Controller
has detected that
operator ran in the
wrong direcon.
Motor wiring. 1. Check motor wiring and
correct, as needed.
2. Press RESET to clear fault.
41 ERROR 3
HY5B FAILED
The SmartDC Controller
has detected a
communicaon error
with a HY5B vehicle
detector.
Caused by removal of HY5B
or lack of integrity of the
socket connecon. This
message will also indicate
which detector the alert
applies to: Exit Loop (ELD),
Inside Obstrucon Loop
(IOLD), Outside Obstrucon
Loop (OOLD), or Center
Loop (CLD)- (User Relay
22).
1. Press RESET.
2. Remove and re-install the
HY5B.
3. Replace the HY5B if needed.