5.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 197
Parameter Details
5
F1-19: dv4 Detection Selection (CLV/PM)
Sets the number of pulses necessary to trigger a dv4 fault when there is a motor speed deviation opposite to the frequency
reference. Setting F1-19 to 0 disables dv4 detection.
Note: A common cause for a dv4 fault is the incorrect setting of E5-11. Make sure the correct encoder offset is set to E5-11.
F1-20: PG Option Card Disconnect Detection 1
Sets whether the drive detects a fault when a speed feedback card is disconnected.
Setting 0: Disabled
Setting 1: Enabled
F1-29: dEv Detection Condition Selection
Selects when dEv error detection is active.
Setting 0: After speed reference, SFS output and motor speed have matched once.
Setting 1: After speed reference, SFS output have matched once.
Setting 2: Always during Run.
Figure 5.15
Figure 5.15 Speed Deviation Detection Conditions Flowchart
F1-50: Encoder Selection
Note: Available in drive software PRG: 7016 or later.
Sets up the type of encoder connected to a PG-F3 option card.
Setting 0: EnDat 2.1/01, 2.2/01 Serial Communications operation + Sin/Cos
Setting 1: EnDat 2.2/22 Serial Communications operation
Setting 2: HIPERFACE
The use of EnDat2.2/22 encoders requires a PG-F3 option with software version 0102 or later.
The use of HIPERFACE encoders requires a PG-F3 option with software version 0104 or later.
To identify the PG-F3 software version refer to the PG-F3 labeling in the field designated “C/N” (S + four digit number).
No. Parameter Name Setting Range Default
F1-19
dv4 Detection Selection
0 to 5000 128
No. Parameter Name Setting Range Default
F1-20
PG Option Card Disconnect Detect 1
0 or 1 1
No. Parameter Name Setting Range Default
F1-29
dEv Detection Condition Selection
0 to 2 2
No. Parameter Name Setting Range Default
F1-50 Encoder Selection 0 to 2 0
Speed reference
Speed
Soft Starter Output and Calculating
the Speed Reference
Motor speed
Setting 2
Setting 1
Setting 0
C
B
A
A
B
C
Time
common_
TMonly